Series 7000 V8
Power Quality & Energy Analyzer
MEASUREMENTS:
VOLTS: P–N & P–P (MIN. AND MAX READINGS AVAILABLE)
AMPS: P–N & P–P (MIN. AND MAX READINGS AVAILABLE)
KW: P–N AND AVERAGE (MIN. AND MAX READINGS AVAILABLE)
MAX. KW, KVA AND AMP-DEMAND (SLIDING WINDOW)
POWER FACTOR: P–N AND AVERAGE
REACTIVE POWER L: (–) P–N AND AVERAGE
REACTIVE POWER C: (+) P–N AND AVERAGE
VOLTAGE HARMONIC: THD%
CURRENT HARMONIC: THD%
FREQUENCY
KWh TOTAL
KVAR–, KVAR+ (HRS)
DATE/TIME
THREE TARIFFS
(P=Potential; N=Neutral)
FEATURES:
5 AMP CT OPERATED
AUTO RANGING (3 OR 4 WIRE, SAME METER)
FIELD PROGRAMMABLE EVENTS
MIN. AND MAX. READINGS TO NINE DIGITS
PUSH BUTTON DISPLAY
LARGE LCD DISPLAYS ALL THREE READINGS ON 1 SCREEN
RS 485 (MODBUS RTU)
TWO PROGRAMMABLE ENERGY OR ALARM RELAYS
SUBMETERING TESTING COMPLIANCE (STC):
REMOVABLE VOLTAGE AND CURRENT TERMINAL BLOCKS FOR EASE OF FIELD VERIFICATION.
CURRENT TRANSFORMERS:
5 AMP INPUT
SEE THE CT SECTION FOR SELECTION
POWER
MEASURING VOLTAGE: 120–480 VC/600 VAC*
VOLTAGE BURDEN: .5 VA
VOLTAGE TOLERANCE: ±20%
FREQUENCY: 35–65 Hz
CURRENT INPUT: 5 AMPS/OPTIONAL 110 mv
CURRENT BURDEN: .75 va
OPERATIONAL TEMPERATURE: –20ºC TO 70ºC
ACCURACY:
POWER: .5%
ENERGY: .2%
ANSI C12.16
RELAYS:
MAXIMUM SWITCH LOAD: 2500 va
VOLTAGE RATING: 240 VAC/48 VDC
PULSE CLOSURE TIME: 80 ms (energy)
ENERGY/ALARMING
STANDARDS:
UL 3111-1, CUL, IEC, CE
FCC CLASS A PART 15
COMMUNICATIONS:
RS-485 — MODBUS RTU
MODELS (3 OR 4 WIRE SAME METER)
K7V8240 120-208-240 VAC
K7V8480 277-480 VAC
K7V8600 346-600 VAC