ENERGY AND POWER TRANSDUCERS

Remote Meter
CTRS 485

General Characteristics
The CTRS 485 is a panel mounting meter for three phase networks, connectable to RS-485 bus with a PC master computer.

The transducer measures the following parameters (see table 1):
a) True RMS values of V, A, PF, W, var (inductive or capacitive)
b) Acumulated energies (kWh, kvarh inductive and capacitive)

A relay output gives pulses according to measures active energy. The radio (pulses / kWh) is programable. A rechargeable battery keeps accumulated energies for over 90 days without supply.

Parameter readings
Several CTRS 485 may be connected to a RS-485 bus and the mesured values may be read in the master PC with the standard software. From one single PC up to 32 peripherals may be addressed and read via RS-485 (converters for RS-232 to RS-485 are available). Maximum bus length is 4000'.

Active energy may also be read from the pulses output, when connected to an external pulse counter or PLC.

Standard software
Standard software includes:
- Setup for communication parameters with bus RS-485.
- Setup of CTRS 485 (transformers ratios, pulses/ kWh, etc.)
- PC data adquisition in a CTRS 485 bus with several peripherals.
- Other programs are available on request.

Functions
Measured parameters:
Parameter L1 L2 L3 L4
rms L1-L2 L2-L3 L3-L1  
rms X X X  
PF X X X  
Hz X      
W X X X  
var L X X X  
var C X X X  
Wh       X
varh L       X
varh C       X

Technical Characteristics

Supply voltage (other on request)230 V or 400 V d.c. / a.c.
Tolerance+10 % / -15 %
Frequency50...60 Hz
Consumption10 VA
Working temperature0 / 50 °C
Measuring circuit: Three-phase
Voltage measuring circuits
Measuring range (automatic scale adjustment)20...500 V a.c.
Current measuring circuits
Measuring range: 5 amp / 1.5 VT
Voltage and current scale factors programmable
Output relay contacts
Resistive load5 A / 250 V
Inductive load0.8 A / 250 V
Accuracy Class
Current0.5 % of reading ± 2 digits
Voltage 0.5 % of reading ± 2 digits
Active power1 % of reading ± 2 digits
Reactive power1 % of reading ± 2 digits
Test conditions:
Errors due to V.T. and C.T. are not included
Temperature+5 / +45 °C
Power factor0.5 A....1
Measured values between 5% and 100% of full scale
Constructive Characteristics
Mounting terminals:
Front mounted
Inside panel, DIN 46277 rail
Serial outputDB-9 front connector
Weight0.65 kg
StandardsIEC 1010-1, EN 61010-1, IEC 521, IEC 664, UNE 21 310, VDE 0110, UL 94
Accessories
Current transformers in 1.5 V (see the CT section)
PC Converter RS-232 to RS-485
Optional Software